
Section 4: Deploying and Operating RS-232 SBE 38
15
Power and Cable Length
There are two issues to consider:
• Limiting the IR loss to 1 volt; higher IR loss will prevent the
instrument from transmitting real-time data because of the difference in
ground potential.
• Supplying enough power at the power source so that sufficient power is
available at the instrument after considering IR loss.
Looking at each issue separately:
Limiting IR Loss to 1 Volt
The limit to cable length is typically reached when the maximum current times
the power common wire resistance is more than 1 volt, because the difference
in ground potential of the SBE 38 and ground controller prevents the SBE 38
from transmitting real-time data.
V
limit
= 1 volt = IR
limit
Where
I = current required by SBE 38 (15 mA for RS-232; 10 mA for RS-485).
Maximum cable length = R
limit
/ wire resistance per foot
Supplying Enough Power to SBE 38
Another consideration in determining maximum cable length is supplying
enough power at the power source so that sufficient voltage is available, after
the IR loss in the cable, to power the SBE 38.
Example 1 – For 18 gauge wire, what is maximum distance to transmit power to RS-232 SBE 38?
Is this controlling factor for maximum cable length if wanting to transmit at 1200 baud?
R
limit
= V
limit
/ I = 1 volt / 0.015 Amps = 67 ohms
For 18 gauge wire, resistance is 0.0064 ohms/foot.
Therefore, maximum cable length is 67 ohms / 0.0064 ohms/foot = 10417 feet = 3176 meters.
Note that 3176 meters > 800 meters (maximum distance SBE 38 can transmit data at 1200 baud), so IR loss is not
controlling factor for this example.
Example 2 – Same as above, but there are 4 SBE 38s powered from the same power supply.
R
limit
= V
limit
/ I = 1 volt / (0.015 Amps * 4 SBE 38s) = 17 ohms
For 18 gauge wire, resistance is 0.0064 ohms/foot.
Therefore, maximum cable length is 17 ohms / 0.0064 ohms/foot = 2604 feet = 794 meters (cable length to SBE 38
furthest from power source).
Note:
Common wire resistances:
Gauge Resistance (ohms/foot)
12 0.0016
14 0.0025
16 0.0040
18 0.0064
19 0.0081
20 0.0107
22 0.0162
24 0.0257
26 0.0410
28 0.0653
Example 1 – For 18 gauge wire, what is maximum distance to transmit power to RS-232 SBE 38 if using 8.5 volt power
source to supply power? Is this controlling factor for maximum cable length if wanting to transmit at 1200 baud?
SBE 38’s input power specification is 8 – 15 volts. Therefore, a 0.5 volt IR drop (8.5 volts – 8 volts) would still provide
enough power to SBE 38.
V = IR 0.5 volts = (0.015 Amps) * (0.0064 ohms/foot * cable length) Cable length = 5208 ft = 1588 meters
Note that 1588 meters > 800 meters (maximum distance SBE 38 can transmit data at 1200 baud), so IR drop in power is
not controlling factor for this example.
Example 2 – Same as above, but there are 4 SBE 38s powered from the same power supply.
V = IR 0.5 volts = (0.015 Amps * 4 SBE 38s) * (0.0064 ohms/foot * cable length)
Cable length = 1302 ft = 397 meters (cable length to SBE 38 furthest from power source).
Note that 397 meters < 800 meters (maximum distance SBE 38 can transmit data at 1200 baud), so IR drop in power is
controlling factor for this example. Using a higher voltage power supply or a different wire gauge (12 or 14 gauge) would
provide sufficient power at SBE 38 to allow 800 meter cable length.
Comentários a estes Manuais